This week we conclude our article series on the challenges of keeping IT equipment cool in high density environments by exploring the importance of rack hygiene and the energy efficiency cost of airflow leakage.
Get the full report.
No matter how well a containment system is constructed and installed, its benefits can be reduced or negated if good “rack hygiene” practices are not followed. Poor practices can cause extreme cases of recirculation within the cabinet resulting in a 10-30°F rise in ITE intake temperatures above the cold aisle supply temperature.
Here are the basics that are relatively easy to implement, and at little or no cost.
In cases where there is a significant disparity in power density and exhaust airflow between opposing cabinets in a common hot aisle, the higher volume and velocity of the exiting airflow from high power cabinets can inhibit the low density cabinets from allowing the hot air to completely exit the cabinets which may cause them to overheat. If this occurs, an upward facing rear deflector on the higher density cabinet (or both cabinets) will help mitigate this issue.
If cabinet overheating occurs, an upward facing rear deflector on the higher density cabinet (or both cabinets) will help mitigate this issue.
MoFlo, courtesy of TechnoGuard
In effect, any supply airflow from the cooling system that is not passing only through the ITE is considered bypass airflow and wasted cooling and fan energy. This is also called oversupply or over ventilation. While it is nearly impossible to accomplish this as a practical matter, to ensure that ITE airflow requirements are met, a certain amount of oversupply is necessary. However, unnecessary and preventable leakage should be controlled wherever possible or practical in high density environments.
While we have been discussing the technical aspects of airflow management, ultimately it also directly translates to increased or decreased fan energy usage and the cost of energy (see Fan Laws).
There are three basic fan laws, which express the how the change in relative fan speed, static pressure and horsepower (power) interact.
Fan Law 1
The change in fan speed is proportional to the change in airflow
Fan Law 2
The change in static pressure (increase/decrease) with the square of the change in airflow
Fan Law 3
The fan power (increases/decrease) with the cube* of the change in airflow (fan speed). (*in reality the exponent of the actual fan curve may be slightly lower than a cube “3” exponent)
The chart in Table 9 shows how bypass airflow can impact the fan energy.
Table 9 – A hypothetical example of relative airflow vs fan power, simplified for clarity *(in reality the exponent of the actual fan curve will be slightly lower that the cube “3” exponent)
Download the entire paper, “High Density IT Cooling – Breaking the Thermal Boundaries“ courtesy of TechnoGuard, for exclusive content, including things to look for when selecting a data center provider.
TL;DR AI is changing the geography of digital infrastructure. Distributed computing, rural connectivity, and growing…
TL;DR Foresight will host a webinar on January 12, 2027, at 11:00 AM ET, exploring…
TLDR: Connecting data centers to education, healthcare research, communications, and business services makes their purpose…
TL;DR Enterprise AI is entering a new phase of adoption. Organizations must demonstrate measurable business…
TL;DR ESI Total Fuel Management has been named a 2026 Tech100 Tech Company Honoree by…
TL;DR: Marketing builds visibility, but public relations builds credibility, and AI is making that difference…